High pressure regulator - Serie HPS100







HPS100

Main features:
  • Medium/high pressure setting
  • High regulation accuracy
  • High flow rate
  • Spring loaded
  • EN 334 compliance
  • Threaded and flanged connections DN 25x25
  • Compact design
  • Easy maintenance
  • Internal or external adjustment

On request:
  • Inlet and outlet pressure gauges
  • Low pressure setting
  • Integrated relief valve
  • External pulse
Application: HPS 100 regulator is suitable to reduce gas pressure for industrial and commercial applications, for medium and high pressure. Designed to deliver high regulation accuracy, this device is suitable for use with non-corrosive gases, previously filtered. HPS 100 regulator is widely used in natural gas, manufactured and LP gas plants, in both civil and industrial installations.

Product information: HPS 100 regulator is direct acting type, controlled by a diaphragm and counter spring. HPS 100 regulator is “top entry” design, which allows an easy maintenance without removing the body from the line.

TECHNICAL FEATURES  
Body size 1"
Connections threaded EN 10226 o NPTF
flanges (on request) PN16-PN40
Inlet pressure range 0,5 ÷ 20 bar / 7,5 ÷ 290 psi
Outlet pressure range 500 ÷ 2800 mbar / 7,25 ÷ 40 psi
Accuracy class AC% 20
Closing pressure class SG% up to 20
Design temperature Ts -20 ÷ +60 °C
Design pressure 200 bar / 290 psi
Acceotable gases Natural gas, town gas, lpg, nitrogen, air non-corrosive gas
Satefy devices Built-in relief valve (optional)
Reference standards-approvals En 334

 

SAND. MATERIALS  
Body Aluminium "anticordal"
Covers Aluminium cast alloys AI Si11 Cu2 (Fe) EN AC 46100
Diaphragm Reinforced rubber 555N - Ag125 AF
Valve seat Aluminium UNI EN 573 EN AW 2011
Shutter Brass CuZn39Pb3 EN12164
Reinforced gasket Vulcanized rubber
Balanced diaphragm Synthetic rubber with canvas
Seals Nitrile rubber O-rings NBR
Springs EN 10270 zinc plated carbon steel

 

DIMENSIONS AND WEIGHTS    
Flanged
PN16/PN40
ANSI150/ANSI300
Threaded
ANSI/ASME B.1.20.1
Threaded
EN 10226

 

CODICE
HPS
CONNECTIONS A
(mm)
B
(mm)
C
(mm)
D
(mm)
E
(mm)
F
(mm)
G
(mm)
Pesi
100 Flanged DN25
X
DN25
183     120 25 140 50 4,5
Threaded
ANSI/
ASME B1.20.1
NPTF
1"X1"
  156   2
Threaded
EN 10226
Rp
1"x1"
    100 1,5

 

TYPICAL NSTALLATION                                     

 

OPERATION AND COMPONENTS                                                

FLOW CAPACITIES    

HPS 100 - MP : 300-750 MBAR
Intel pressure Pu Gas natural portata-capacity Q[stm3/h]
AC = 20%
LPG/GPL portata - capacity Q [Kg/h]
AC = 20%
1 bar 54 65
1,5 bar 85 100
2 bar 100 120
2,5 bar 115 140
3 bar 130 160
3,5 bar 145 175
4 bar 160 195
5 bar 180 215

HPS 100 - TR : 800-1750 MBAR
Intel pressure Pu Gas natural portata-capacity Q[stm3/h]
AC = 20%
LPG/GPL portata - capacity Q [Kg/h]
AC = 20%
1 bar 45 55
1,5 bar 75 90
2 bar 100 120
2,5 bar 135 160
3 bar 160 195
3,5 bar 175 210
4 bar 200 240
5 bar 230 275

HPS 100 - TR : 2000-2500 MBAR
Intel pressure Pu Gas natural portata-capacity Q[stm3/h] AC = 20% LPG/GPL portata - capacity Q [Kg/h] AC = 20%
2,5 bar 55 65
3 bar 85 100
3,5 bar 135 160
4 bar 160 195
6 bar 230 275

The above tables give the maximum flow capacity - in m3/h at standard conditions of absolute pressure of 1.013 bar and 15°C temperature.

NOTES:
Capacity Q [m3/h] = referred to Natural Gas at lowest value of setting range
Conversion to: LPG capacity in kg/h= multiply by 1,2
Azote capacity = multiply by 0,789
AC = accuracy class
Regulators must not exceed 20 m/s speed flow on outlet.











Réducteurs de pression